Powador 72.0 TL3 Park NEW!
Powador 720 TL3 with a maximum AC power of 60.000 VA. Suitable as a single unit for PV installations with a generator power of up to 72.000 W.
The Powador 72.0 TL3 Park is availbale from Q3/2013.
Electrical Data
| Input Variables | |
|---|---|
| Max. recommended PV generator power | 72.0 kW |
| MPP range | 200 V … 850 V* |
| Starting Voltage | 250 V |
| No-load voltage | 1,000 V |
| Max. input current | 3 x 36.0 A |
| Max. power / tracker | 30 kW |
| Number of strings / MPP controller | 3 x 1 based on design M / 3 x 5 based on design XL |
| Number of MPP controllers | 3 |
| Output Variables | |
| Rated output | 60,000 VA |
| Line voltage | acc. to local requirements |
| Safety cut-out | |
| Rated current | 3 x 72.2 A |
| Rated frequency | 50 Hz / 60 Hz |
| cos phi | 0.80 inductive ... 0.80 capacitive |
| Number of grid phases | 3 |
| General Electrical Data | |
| Max. efficiency | 98.0% |
| European efficiency | 97.8% |
| Night consumption | ≈ 1.5 W |
| Switching plan | self-inverted, transformerless |
| Grid monitoring | acc. to local requirements |
Mechanical Data
| Display | graphical display + LEDs |
| Control units | 4-way navigation + 2 buttons |
| Interfaces | Ethernet, USB, RS485, S0 output |
| Ambient temperature | -20 °C … +60 °C ** |
| Temperature monitoring | > 75 °C temperature-dependent impedance matching, > 85°C cut-out |
| Fault signalling relay | potential-free NOC max. 230 V / 1 A |
| Connections | AC connection via screw terminals, bushing 1 x M50, max cross section: 50 mm² (flexible); DC connection of M version: spring-type terminals 6-35 mm²***; DC connection of XL version: screw and spring-type terminals 10 mm², bushing 6 x M 32 |
| Cooling | forced cooling / RPM-regulated fan, max. 600 m³ / h |
| Protection class | IP54 |
| Noise emission | 58 dB (A) (only fan noise) |
| DC-switch | integrated |
| Casing | sheet steel |
| H x W x D | 1,360 x 840 x 355 mm |
| Weight | 165 kg |
* The possible input power is reduced at voltages lower than 580 V. The input current is limited to 36.0 A per input
** Power derating at high ambient temperatures
*** Only in conjunction with external Powador Mini-Argus
** Power derating at high ambient temperatures
*** Only in conjunction with external Powador Mini-Argus
Subject to change without prior notice (10/2012)
Data sheet
| Data sheet Powador 72.0 TL3 ParkFormat:
PDF Size: 138.33 KB Version: 130102 | ![]() ![]() |